Operating room is a sterile zone in the hospital that controls 17-27 °C temperature and 45-55% RH humidity. The main feature of the operating room is to reduce contaminated microorganism, diseases, bacteria, virus, spore-forming to fungi, mold, mites, and dust. Bacteria and other biological contaminants control and keeping relative humidity between 40 % to 60 %. The Air Handling Unit shall supply by an uncontaminated clean air by replacement air flow in the operating room. That air flows pass through HEPA filtration system with 99.9999% efficiency to remove airborne contamination. HEPA filter located on the ceiling above the surgical table and other surgical instruments. Absolutely, those clean fresh air must supply by efficiency air handling unit with special design and produced to suit for operating room function.
Air handling is the equipment to collect air from operating room return duct, mixing with new fresh air in the mixing box or mixing chamber. Delivery those air to pre-filter, filtering again by the medium filter. Cooled it by cooling coil system in order to reduce the temperature.Pass through the humidity control equipment which connect to cooling system. Distribute by air duct to the operating room through HEPA filter to sterile zone.
There are several questions in the different AHU function of normal indoor airsuch as office, rooms in a house, department store or buildings and operating rooms. The major difference is normal indoor air condition doesn’t precision control humidity. Humidity which over 60% RH will be a cause of the proliferation of bacteria and other biological contaminants. Situative humidity control of operating room settles at 45-55% RH. It needs additional equipment in AHU for humidifying and dehumidifying of air. Hot gas reheat system or heat pipe system is adding design by specialist in order to work properly with the cooling system for this humidity control solution.